Description
KOHLER POWER SYSTEM STAND-BY DIESEL DRIVEN GENERATOR
Model 40REOZJ, Serial number 611080
Specification PA 189231, Engine Model T4045DF150D / T04045D805816X
TOTAL HOURS USED 67 hours Serial Number Transfer Switch K89500
SPECIFICATIONS:
GENERATOR: KW K.V.A P.F.
44.00 55.00 0.8
Voltage 120 / 240 139 /240 127 / 220 120 / 240
Code (61) 1P 51 51 01
Voltage 277 / 480 220 / 380 347 / 600 110 / 220 110 / 190
Code (71) (81) (91) (01) (51)
Voltage 120 / 220 230 / 400 240 /416
Code (51) 1P (71) (71)
Phase Single & Three
Cycles (Hz) 60
ENGINE, DIESEL: John Dear
Engine conforms to 2000 Model Year US EPA regulations on heavy duty
none road diesel cycle engine.
Fuel Rate 66.4 mm ³ / stroke @ 75 hp. (53 KW) @ 1800 rpm
CONTROLS:
Hertz Meter. AC Volt & Amperes Meters. Hour Usage Meter. Oil Pressure Gage.
Water Temp Gage. Battery Meter. Run – Off / Reset – Auto Switch. Battery Tender (Advance
Battery Charging System). Output 12VDC, Input 90 to132 VAC, 50/60 Hz.
Lamp / Test Switch. Silence Normal Alarm Switch. Upper & Lower Meter Scales Switch.
Prealarm High Engine Temperature Light. Pre Alarm Low Oil Press Light.
Low Water Temperature Light. Low Fuel Light. Alarm Buzzer. Low Oil Pressure Light.
High Engine Temperature Light. Emergency Stop Light. Overspeed Light. Auxiliary Fault Light.
Battery Charger Fault Light. Low Battery Voltage Light. Overcrank Light.
High Battery Voltage Light. Air Damper Light. System Ready Light.
EQUIPPED WITH: Decision-Maker 3+ 16 Light Controller.
Kohler Automatic Battery Charger Part D-292863. Diesel Block Heater. Safety Breakers.
77 gallons Diesel Fuel Storage Tank. (4) Vibration Isolation Pads mounted below unit.
Kohler Programming Power Transfer Switch System: Part Number K-566341-70, 100B, 23G,
29V, 34A, 34J, 34Z, 70 Amps. 480 volts, 3 phase, 4 wire, 60 hertz, 3 pole with: REMOTE /
LOCAL Keyed Switch. PROGRAMMING KEYS. TIME DELAY LIGHTS: On – End – Engine Start,
Normal to Emergency, Emergency to Normal, Engine Cooldown. Contactor Positions: Normal
light, Emergency Light. SOURCE AVAILABLE: Normal & Emergency Light. SYSTEM STATUS
LIGHTS: Not in automatic Light, System Alert Light. ACCESSORY ACTIVE: Plant Exerciser Light,
Load Shed Light
COMPLETE FACTORY SAFETY GUARDS
Generator Dimensions 31″ F-B x 82″ L-R x 89½” Height.
Transfer Switch Dimensions 14⅜” F-B x 26″ L-R x 35¾” Height.